Product introduction:
YNY - Ⅲ AC/DC insulation monitor is applicable to DC systems below 1000V and AC ungrounded systems below 1150V. It can be applied to photovoltaic inverters, mining machinery, electrical equipment, electric vehicle charging devices, UPS power supply systems, DC power supply systems in communication industry, and any AC and DC ungrounded systems. The instrument is interlocked with the circuit contactor or the auxiliary contact of the circuit breaker to realize the isolation of the insulation monitor from the power grid when the motor circuit is powered on, and the insulation monitor automatically starts to monitor the insulation of the line when the line is powered off
Product parameters:
Input voltage: AC 85-264V (40… 400Hz) or DC 9-36V (choose one)
Normal consumption: about 4VA
Network voltage: DC 0-1000V or AC 0-1150V
Set alarm value: alarm 1:10-1000k alarm 2:10-2000k
Internal AC resistance value: > 400 K&Omega
Internal DC resistance value: > 400 K&Omega
Internal test voltage:+/- 24V
Maximum test current (R=0): < 0.1mA
Maximum allowable noise DC voltage: DC 1200 V
Line-to-ground capacitance value: 1… 100 μ F
Operating time: under 20uF line-to-ground capacitance< 120S; Under 100uF line-to-ground capacitance< 720S
Measurement accuracy: 5%
Contacts: 2 groups of independent normally open contacts correspond to 2 groups of alarm signals
Maximum switching capacity: AC 230V, 5A or DC 30V 3A
Maximum power-on capacity: AC 230V, 2A or DC 30V 2A
Analog output: 4~20mA corresponds to 0~10M (can be customized according to customer needs)
485 communication output: RS485 communication interface, supporting Modbus RTU protocol
Operation mode: continuous operation
Operating temperature range: - 25 ℃ -+60 ℃
Product dimension drawing is as follows:
The product connecting line is as follows:
Product application:
The product is applicable to frequency converter, charging pile, mine, and other industries.
charging pile
frequency converter
mine